VFD-duty motors · 0.55–315 kW · YVF2 / YXVF

A motor on a drive is not a standard motor

A variable-frequency drive changes more than the speed. It changes how the motor is cooled at low speed, what the winding insulation has to survive, where the current goes in the bearings, and which part of the torque curve you are allowed to use. The YVF2 / YXVF series is built for that duty from the frame up.

Four things a general-purpose motor gets wrong on a drive

Bolting a VFD onto a standard YE3 works — for a fan running at 80–100% speed. It stops working when the duty spends real hours at low speed, in a hot plant, on a long cable, or at constant torque. The failure is rarely immediate; it shows up as a winding that smells hot after eighteen months.

What the drive doesWhat it breaks on a standard motorWhat the VFD motor does instead
Runs below base speedThe shaft-mounted fan moves almost no air at 30% speed, so the winding cooks at exactly the moment the load is highestIndependent constant-speed cooling fan (IC416) — full airflow at any rotor speed
Switches at 4–16 kHzPWM pulses arrive as a steep wavefront; on a long cable the reflected wave can nearly double the peak voltage at the terminalsInverter-grade magnet wire and reinforced turn/phase insulation, rated for the pulse stress
Creates common-mode voltageShaft voltage discharges through the bearings and erodes the racewayInsulated bearing on the non-drive end and a shaft grounding path on the larger frames
Holds constant torque at low speedSelf-ventilation and the standard thermal margin run out; the motor cannot hold the loadThermal design and fan sized for continuous constant-torque duty across the stated range

This is why the two products are not interchangeable on paper even when the nameplate kW matches. The frame may be the same; the cooling, insulation system and bearing arrangement are not.

At a glance

  • YVF2 general VFD duty: 0.55–315 kW, frame 80–355
  • YXVF high-efficiency VFD duty: 0.75–375 kW, frame 80–355
  • 2, 4, 6 and 8 poles; 380 V as standard
  • Independent cooling fan, IC416, full airflow down to minimum speed
  • Insulation class F standard, H on request; IP55
  • Constant torque below base speed, constant power above
  • Explosion-proof VFD duty (YBBP, Ex d) quoted per area classification

Where they go

Pumps, fans, conveyors, mixers

Any duty where the flow or the process sets the speed instead of the mains: boiler feed on sliding pressure, mine dewatering on varying inflow, aeration on dissolved-oxygen control, slurry transfer on density, cooling-tower fans on wet-bulb.

Typical base frequency50 Hz
Typical speed range5–100 Hz
DutyS1, continuous

Type spectrum

VFD-duty series

Same IEC frames as the YE series, so the motor still lands on the existing baseplate — but the cooling and insulation system are specified for drive supply, not for the mains.

SeriesDutyPowerFramePolesCoolingTypical use
YVF2General VFD duty, constant torque below base speed0.55–315 kW80–3552, 4, 6, 8IC416 independent fanPumps, fans, conveyors, mixers on a drive
YXVFHigh-efficiency VFD duty0.75–375 kW80–3552, 4, 6, 8IC416 independent fanContinuous duties where the kWh bill dominates
YBBPFlameproof VFD duty, Ex dQuoted per area classificationPer Ex schedule2, 4, 6, 8IC416 independent fanFlammable-gas areas: gas boosting, refinery, solvent plants

Above about 300 kW the cable and switchgear for 380 V become the expensive part of the installation; a high-voltage YKK machine (160–2,500 kW, 6/10 kV) can be supplied for drive duty with the drive and the winding insulation co-specified. Ranges above are supply envelopes, not model commitments — the exact model is fixed against the duty point at quotation.

Duty envelope · indicative

Torque, speed and the limits in between

A drive-duty motor is normally sold as constant torque below base speed and constant power above it. What that means for a pump is simple: below base speed you can hold any head the pump can make at that speed; above it you get more flow but the torque falls away.

RegionRange (typical)What is availableWhat to watch
Constant torque5–50 HzRated torque continuously, with full cooling from the independent fanMinimum continuous speed is set by the driven machine, not only by the motor — check pump lubrication and bearing film
Constant power50–100 HzRated power, torque falls in inverse proportion to speedAbove base speed the mechanical limits of the driven machine matter more than the motor
Below minimum< 5 HzShort-term only, or not at allLow-speed continuous duty needs a different thermal arrangement; ask before assuming
Skip bandsCase by case—The drive is programmed to jump critical speeds of the train; we need the shaft and baseplate data

A pump or fan load is quadratic: at 80% speed the shaft power is about half, at 50% speed about one eighth. That is the whole economic case for the drive — the motor only has to survive the trip down there.

When a standard motor plus a drive is enough

We would rather sell the cheaper answer when it is the right one. A general-purpose YE3 or YE4 on a drive is a sensible choice when all of the following hold:

  • The duty stays above roughly 70% of rated speed for most running hours
  • The load is quadratic (centrifugal pump or fan), not constant torque
  • Starts and stops are infrequent, and the ambient is normal
  • The motor-to-drive cable is short and the drive output is filtered if it is not

Specify VFD duty when any of these is true:

  • Continuous operation below about 50% speed
  • Constant-torque load — positive-displacement pumps, conveyors, mixers, crushers
  • High ambient, high altitude, or a hot enclosure
  • Frequent starts, high switching frequency, or a long cable run to the motor

What we need to quote one

  • Duty point — kW at the shaft at rated speed, and the driven machine's curve
  • Speed range — minimum and maximum operating speed, and how long is spent at each
  • Load type — quadratic or constant torque; starting torque if it is heavy
  • Supply — voltage, frequency, phases; 380 V or 6/10 kV
  • Drive — make and model, or let us select it with the motor
  • Installation — cable length from drive to motor, ambient, altitude, indoor/outdoor, IP requirement
  • Area classification — safe area, or the Ex zone and gas group
  • Extras — encoder, winding and bearing RTDs, space heaters, brake, terminal box position

Send the existing nameplate and the drive model and we will come back with the equivalent YVF2 / YXVF frame, the cooling arrangement, the minimum continuous speed and the torque available at your lowest operating point.

As a package

Motor, drive, panel and pump as one train

The failure modes on a VFD-driven train are interface failures: the drive's overload setting against the motor's thermal time constant, the cable against the winding insulation, the minimum speed against the pump's bearing film. Buying them from one place puts that interface on one drawing. The motor can also ship on its own, with or without a drive — a replacement on a palm oil mill's EFB line or screw press is the usual case.

01 · Drive selection

Sized to the duty, not the nameplate

Heavy-duty overload margin, switching frequency, and the actual cable length are part of the selection — not left to whoever supplies the drive.

02 · Cable and filter

Long runs get a filter

Above the drive manufacturer's cable limit we add a dv/dt or sine filter, or specify a reinforced winding. The motor is ordered to match the decision.

03 · Panel

One enclosure, one set of drawings

Drive, breaker, line reactor, cooling and terminals assembled and tested as a panel, not shipped as loose components.

04 · Commissioning

Aligned and run before shipment

Pump, motor, coupling and baseplate aligned; the train run at minimum, base and maximum speed before it leaves.

Compliance

Efficiency, and what we will not claim

The IE classes in GB 18613-2020 are written for line-start machines. For a motor running from a drive, the meaningful figure is the type-test efficiency at the speed and load where it actually runs, and we state the standard and the test point it was measured against. We do not label a VFD-duty motor with an IE class borrowed from its line-start equivalent. Market certifications — CE, EAC, UL/CSA or a hazardous-area approval — are quoted item by item against the motor, the drive, the voltage and the country of installation.

Tell us the speed range, not just the kW.

Minimum speed, maximum speed, load type and cable length decide whether the answer is a standard motor on a drive or a VFD-duty machine. We will tell you which, and why.

Ask for a VFD motor selection